Three fixed frequencies, a predictable load ladder and a protective resistor built into the booster - for 35 kV cable withstand testing.
The XHDP-80 is the fixed-frequency 80 kV set in the range, rated 80 kV and 30 mA peak. It is used for AC withstand voltage testing of 35 kV cables and comparable insulation, where the operator wants a predictable output frequency rather than an instrument that selects one. Output is available at 0.1 Hz, 0.05 Hz and 0.02 Hz, with load capability of 1.1 µF, 2.2 µF and 5.5 µF at those frequencies, and a 20 A supply fuse.
| Model | Rated voltage / current | 0.1 Hz | 0.05 Hz | 0.02 Hz | Supply fuse |
|---|---|---|---|---|---|
| XHDP-80 | 80 kV / 30 mA (peak) | ≤ 1.1 µF | ≤ 2.2 µF | ≤ 5.5 µF | 20 A |
The booster body contains a high voltage output protective resistor as part of the design. On site this removes the need to connect an additional protective resistor in the output circuit - one less item to transport, wire and verify before a test.
Current, voltage and waveform are sampled directly at the high voltage side, so the readings reflect what the specimen actually sees. If the output exceeds the set voltage limit the instrument shuts down in under 20 ms. Over-current protection works on both sides: the high voltage side trips at its configured value and the low voltage side trips if current exceeds its rating, both within 20 ms. Boost, step-down, measurement and protection run automatically under microcomputer control, with manual intervention available during the boost.
| Parameter | Value |
|---|---|
| Output voltage range | 0 – 80 kV |
| Output frequency | 0.1 Hz, 0.05 Hz, 0.02 Hz |
| Measurement accuracy | 3 % |
| Positive and negative peak voltage error | ≤ 3 % |
| Waveform distortion | ≤ 5 % |
| Protection operating time | ≤ 20 ms |
| Supply | AC 220 V ± 5 %, 50 Hz |
| Service conditions | Indoor or outdoor, −10 °C to +40 °C, humidity ≤ 85 % RH |
1.1 µF at 0.1 Hz, 2.2 µF at 0.05 Hz and 5.5 µF at 0.02 Hz. Specimens above these limits need the automatic-sweep 80M or a higher-capacity configuration.
The 80 kV peak rating covers 35 kV cable work with margin. The actual test voltage and duration follow the standard applied on site, and the value is entered before the run.
Over-voltage shutdown and over-current protection on both the high and low voltage sides, each acting within 20 ms, plus the high voltage protective resistor built into the booster.
This unit uses three fixed frequencies and carries 1.1 – 5.5 µF. The 80M sweeps 0.1 – 0.01 Hz automatically and carries up to 6 µF below 50 kV and 4 µF above on its 80 kV rating.
Tell us the cable class and the capacitance per phase. If your specimens fall inside the 1.1 – 5.5 µF ladder we will confirm this set; if not, we will say so and point you to the 80M.